BK1120 | EtherCAT Coupler for standard Bus Terminals
Published on : Tuesday 30-11--0001
The BK1120 Bus Coupler connects EtherCAT with the K-bus components (KLxxxx) from the proven Beckhoff Bus Terminals range. One station consists of a BK1120 Bus Coupler, any number of terminals (up to 64; up to 255 with K-bus extension) and a bus end terminal.
The Bus Coupler recognises the connected terminals and automatically allocates them into the EtherCAT process image. The Bus Coupler is connected to the network via the upper Ethernet interface. The lower RJ45 socket may be used to connect further EtherCAT devices in the same strand.
In the EtherCAT network, the BK1120 Bus Coupler can be installed anywhere in the Ethernet signal transfer section (100BASE-TX) – except directly at the switch. The coupler BK9000 (for K-bus components) is suitable for installation at the switch.
Specifications
Technical data |
BK1120 |
---|---|
Task within EtherCAT system |
coupling of standard Bus Terminals (KLxxxx) to 100BASE-TX EtherCAT networks |
Data transfer medium |
Ethernet/EtherCAT CAT5 cable |
Distance between stations |
100 m (100BASE-TX) |
Number of Bus Terminals |
64 (255 with K-bus extension) |
Max. number of bytes fieldbus |
1,024 byte input and 1,024 byte output |
Protocol |
EtherCAT |
Data transfer rates |
100 Mbaud |
Configuration possibility |
via KS2000 or EtherCAT (ADS) |
Bus interface |
2 x RJ45 |
Power supply |
24 V DC (-15 %/+20 %) |
Input current |
70 mA + (total K-bus current)/4, 500 mA max. |
Starting current |
approx. 2.5 x continuous current |
Recommended fuse |
≤ 10 A |
Current supply K-bus |
1,750 mA |
Power contacts |
24 V DC max./10 A max. |
Electrical isolation |
500 V (power contact/supply voltage/Ethernet) |
Weight |
approx. 150 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. |
IP 20/variable |
Approvals |
CE, UL, Ex |
It is used in Process Industries.
BECKHOFF Automation Pvt Ltd.Tel:+ 91 20 / 40 00 48 00, Email: [email protected]